AWR eBooks

Conquer Radio Frequency

Issue link: https://resources.system-analysis.cadence.com/i/1326562

Contents of this Issue

Navigation

Page 46 of 228

2.3 Transmission Lines – an Introduction 41 Figure 2.3-7 Two-wire transmission line For a parallel-wire line with air insulation, shown in Figure 2.3-7, the characteristic impedance may be calculated as shown: √ Where, Z0 = Characteristic impedance of line d = Distance between conductor centres r = Conductor radius = Relative permittivity of insulation between conductors Figure 2.3-8 A coaxial transmission line If the transmission line is coaxial 14 in construction (Figure 2.3-8), the characteristic impedance follows a different equation: √ Where, Z0 = Characteristic impedance of line d1 = Inside diameter of outer conductor d2 = Outside diameter of inner conductor = Relative permittivity of insulation between conductors In both equations, identical units of measurement must be used in both terms of the fraction. If the insulating material is not air (or vacuum) both the characteristic impedance and the propagation velocity will be affected. The ratio of a transmission line's true propagation velocity and the speed of light in a vacuum is called the velocity factor of the line. The velocity factor is purely a factor of the relative permittivity (or dielectric constant) of the insulating material which is defined as the ratio of a material's electric field permittivity to that of a pure vacuum. 14 Coaxial lines are explained further in section 2.11.1 (2.3-1) (2.3-2) Conquer Radio Frequency 41 www.cadence.com/go/awr

Articles in this issue

Links on this page

view archives of AWR eBooks - Conquer Radio Frequency